ETCLO-830 Compressor Safety Controller

The ETCLO-830 Compressor Safety Controller has an anti-short cycle, solenoid valve time delay and lead-lag multi-settings. It is designed for use with any single and two-stage air conditioning and refrigeration equipment for compressor operation and protection control. If during normal operation any safeties are opened (low or high pressure switches), the compressor will shut off immediately. The controller then restarts the A/C unit again and a warning flag will be set. The compressor will be locked-out if safeties are opened for a second time. Manually opening and closing the thermostat can restart the A/C unit and reset the board. The fault can be attended to at any convenient time. The early warning feature will save the compressor from burnout.

buton download pdf buton download drawing

  • Microprocessor-based controller
  • Random start of 0-60 seconds to avoid simultaneous start of several units after power interruption
  • Anti-short cycle time delay (selectable 0, 3, 5 or 10 minutes)
  • Relay output for solenoid valve operation
  • Time delay settings for solenoid valve (selectable 0, 10, 30, 60 or 90 seconds)
  • Time delay of 30 seconds between the two compressors
  • Built-in automatic warning flag setting to monitor the fault for a period of 30 minutes from the first fault signal
  • Manual and automatic setting for compressor rotation (lead-lag sequence changeover) including runtime, every 15 days or every 30 days with automatic changeover
  • TRIAC fault output for alarm signal
  • LED status indicators (power and fault)
  • On board test mode jumper for fast testing and diagnostic
  • Input power supply: 24VAC, 50/60 HZ
  • Power consumption: 4 VA @ 24 VAC (board only)
  • Output (compressor): SPST relay contact
  • Output (fault): Solid state, TRIAC
  • Relay output current: 1000 mA continuous
  • Operating conditions: -40 to +167°F Temp, 10% to 90% RH
  • Dimensions (LxWxH): 4” x 3.375” x 1.375” Mounted in Snap-Track (provided)

During normal operation of the compressor, contacts 5 and 6 will be energized, as well as the safety contacts that are in series with contact 6 and the compressor’s contactor. In this state, the warning flag (in the processor’s memory) will remain reset and normal operation will continue.

If during normal operation safety contact(s) opens, the warning flag will be set and the compressor will shut off immediately. Terminals 5 and 6 will open for the duration of the selected anti-short cycle time delay (ASTD). Upon completion of this delay, contact 5, followed by 6, will re-energize. At this time there are two possible outcomes to this scenario:

A - If the safety contact(s) is still open, the board will immediately go into lock-out mode, so that contacts 5 and 6 will be opened and the TRIAC output at terminal 4 (alarm output) will be activated.

OR

B - If the safety contact(s) is now closed, the compressor will start running again. However, the warning flag will remain set. If a safety contact(s) opens, the related compressor will immediately go into lock-out mode.

Under condition B, the warning flag will be reset after 30 minutes of successful running of the compressor. In test mode, the 30 minutes for warning flag will be reduced to 4 seconds.

When the thermostat is satisfied, the warning flag will be reset.

The board is equipped with one green LED that indicates power to the board. Two red LEDs indicate the lock-out condition for each compressor.

After power interruption, a unique time delay of 0–60 seconds for random start begins to avoid simultaneous start of multi-unit applications.

ETCLO-830

Terminal Designation

Terminal Designation

Jumper Settings

Three sets of five position jumpers (J1, J2 & J3) are used to select functions as per tables below. Only one shunt should be applied to each jumper (except J3 in test mode).

Jumper Settings

The ETCLO-830 is designed for class 2 circuits and should be powered by an UL recognized class 2 24 VAC transformer.


ETCLO-848

The ETCLO-848 Compressor Safety Controller with fixed anti-short cycle delay is designed for use with any single stage air conditioning and refrigeration equipment as compressor protection. If during normal operation any safeties are opened (low or high pressure switches), the compressor will shut off immediately, and then the controller manages the restart of the A/C unit and a warning flag will be set. The compressor will lock-out if safeties are opened for a second time. Manually opening and closing the thermostat can restart the A/C unit and reset the board. The fault can be attended to at any convenient time. The early warning feature will save the compressor from burnout.

buton download pdf buton download drawing

  • Microprocessor-based controller
  • Anti-short cycle timer delay (3 or 5 minutes fixed)
  • Built-in automatic warning flag setting to monitor the fault for a period of 30 minutes from the first fault signal
  • TRIAC output fault for alarm signal
  • LED status indicators (power and fault)
  • Input power supply: 24VAC, 50/60 HZ
  • Power consumption: 4 VA @ 24 VAC (board only)
  • Output (compressor): SPST relay contact
  • Output (fault): Solid state, TRIAC
  • Relay output current: 1000 mA continuous
  • Operating conditions: -40 to +167°F Temp, 10% to 90% RH
  • Dimensions (LxWxH): 2” x 2.375” x 1.250” Mounted in Snap-Track (provided)

When the thermostat demands for cooling, terminal 3 will be energized. Assuming that all safeties (HP & LP) that are connected in series with terminal 3 are closed, the warning flag (in the processor memory) will remain reset and normal operation will continue.

If during normal operation (thermostat contact closed) any safeties contact(s) opens, the warning flag will be set, the compressor will be shut off immediately and terminal 3 will open. This state will remain for the duration of the selected anti-short cycle delay.

Upon completion of the anti-short cycle delay, terminal 3 will re-energize. At this time, the controller monitors the operation of the safeties and takes decision based on:

A - If the safety contact(s) are still open, the board will immediately go into lock-out mode, so that terminal 3 will be opened, and the TRIAC output at terminal X will be activated (board will go into lock-out mode).

OR

B - If the safety contact(s) are now closed, the compressor will start running again. The warning flag will remain set. If safety contact(s) opens, the board will forfeit the anti short cycle delay and will immediately go into lock-out mode.

The warning flag will be reset after a 1⁄2 hour (30 minutes) of successful continuous compressor running.

Also, when the thermostat is satisfied, the warning flag will be reset.

The board is equipped with two LEDs. The green LED indicates power to the board. The red LED indicates the lock-out condition.


ETCLO-832 Compressor Safety Controller

The ETCLO-832 Compressor Safety Control has an anti-short cycle, pump down solenoid valve time delay and lead lag multi settings. It is designed for use with any single and two-stage air conditioning and refrigeration equipment for compressor operation and protection control. If during normal operation, any safeties are opened (low or high pressure switches), the compressor will shut off immediately. The controller then restarts the A/C unit again and a warning flag will be set. The compressor will be lockout if safeties opened for second time. The A/C unit can be restarted manually by opening and closing the thermostat contact, which reset the board. The fault can be attended to at any convenient time. The early warning feature will save the compressor from burn out.

buton download pdf

  • Microprocessor based controller.
  • Random start of 0-60 seconds to avoid simultaneous start of several units during power interruption.
  • Anti-short cycle time delay (0, 3, 5 or 10 minutes) selection.
  • Relay output for pump down solenoid valve operation.
  • Time delay settings for pump down solenoid valve (0, 10, 30, 60 and 90 seconds).
  • Time delay of 30 seconds between the two compressors.
  • Built in automatic warning flag setting to monitor the fault for a period of 30 minutes from the first fault signal.
  • Manual and automatic setting for compressor rotation (lead-lag sequence change-over).
  • Five settings include runtime; every 15 days or every 30 days with automatic change over.
  • TRIAC fault output for alarm signal.
  • LED status indicators (power and fault).
  • On board test mode jumper for fast testing and diagnostic.
  • Input power supply: 24VAC, 50/60 HZ
  • Power consumption: 4 VA @ 24 VAC (board only)
  • Output (compressor): SPST relay contact
  • Output (fault): Solid state, TRIAC
  • Relay output current: 1000 mA continuous
  • Operating conditions: -40 to +167°F Temp, 10% to 90% Humidity (non condensing).
  • Dimensions (LxWxH): 4” x 3.375” x 1.375” Mounted in Snap-Track (provided)

The ETCLO-832 is provided with full size Snap Track for easy installation.

ETCLO-832

 

 


 

ET-793

A unique electronic controller design using one sliding damper to function as a return and fresh air mixing process instead of using two separate dampers. This design utilizes one actuator for one damper for both fresh air and return air.

The controller is designed to operate a 12 VDC actuator to slide the damper to the required position. The controllers receive inputs from supply air temperature and outdoor temperature or enthalpy digital signal.

One damper control system saves cost and space in the packaged air conditioning unit.


Economizer ET-757

One of the challenges that HVAC design engineers face is developing an air conditioning distribution system to deliver outdoor air to the occupants of a building. This task involves determining whether the outdoor air is acceptable for a free cooling system, and then developing an air intake and mixing control system that will deliver the needed amount of outdoor air to the building at an acceptable cost.

This challenge can easily be met with the Economizer Controller ET-757. This controller allows a cooling air handler to supply outdoor air instead of re-circulated air in order to reduce or eliminate the need for a mechanical cooling system during mild or cold weather. If the outdoor air is below the high enthalpy (humidity and temperature) point as set on the board, and based on an analog signal from the enthalpy sensor, the controller will lock-out the compressor (mechanical cooling) and modulate the return and outdoor air dampers to maintain the cooling set point. When the outdoor air enthalpy exceeds the high enthalpy set point, the outdoor air damper moves to the set minimum position for ventilation. The ET-757 meets the requirements of AINSI/ASHRAE/IESNA Standard 90.1-2001, “Energy Standard for Buildings Except Low-Rise Buildings”.

Energy saving and improved air quality make the ET-757 attractive to HVAC design engineers and building owners, not to the mention the fact that a system with such a controller usually pays for itself within one or two years.

buton download pdf ET-757 Drawing 1ET-757 Drawing 2

  • Microprocessor-based controller for high accuracy and flexibility
  • Enthalpy Controller input (4-20 mA signal)
  • Supply or mixed air temperature input
  • Input terminals for G (fan switch), Y1 (cooling 1st stage) and Y2 (cooling 2nd stage) from thermostat
  • Output terminals for B (blower), C1 (1st stage compressor) and C2 (2nd stage compressor) to the A/C equipment
  • Free cooling hour counter output for saving energy verification
  • On-board potentiometers for easy field setup and adjustment of:
    • OAD minimum outdoor air damper setting range 0% to 100%
    • STS, supply air temperature setting, range 50 to 60°F
    • EHS enthalpy limit (four levels: A, B, C, & D)
  • On-board LED status indicators for:
    • Free cooling
    • Controls, faults and diagnostics
  • Built-in 45-second indoor fan purge delay
  • Use the outdoor air as an emergency cooling stage after 30 minutes if mechanical cooling does not meet the cooling demand
  • Built-in time delay of 30 seconds between the two compressors
  • Built-in compressor anti-short cycle time delay (3 minutes)
  • Mounted in snap-track for easy installation


ET-858

One of the challenges that HVAC design engineers face is developing an air conditioning distribution system to deliver outdoor air to the occupants of a building. This task involves determining whether the outdoor air is acceptable for a free cooling system, and then developing an air intake and mixing control system that will deliver the needed amount of outdoor air to the building at an acceptable cost.

This challenge can easily be met with the Economizer Controller ET-858. This controller allows a cooling air handler to supply outdoor air instead of re-circulated air in order to reduce or eliminate the need for a mechanical cooling system during mild or cold weather. If the outdoor air is below a high enthalpy (humidity and temperature) limit, typically 28 BTU/lb or 75°F db, the controller will lock-out the compressor (mechanical cooling) and modulate the return and outdoor air dampers to maintain the cooling set point. When the outdoor air enthalpy exceeds the high limit set point, the outdoor air damper moves to the set minimum position for ventilation.

ET-858 can also control the amount of fresh air needed for ventilation by means of an analog signal from an indoor air quality sensor. This is to meet the Demand Control Ventilation (DCV) requirement. The indoor air quality sensor (typically CO2 sensor) determines the demand for fresh air based on the occupancy of the building by measuring the amount of CO2 (unlike a fixed rate of fresh air for maximum occupancy). The ET-858 meets the requirements of AINSI/ASHRAE/IESNA Standard 90.1-2001, “Energy Standard for Buildings Except Low-Rise Buildings”. More details on DCV can be found at the Learning Centre.

Energy saving in DCV and improved air quality make the ET-858 attractive to HVAC design engineers and building owners, not to the mention the fact that a system with such a controller usually pays for itself within one or two years.

buton download pdf ET-757 Drawing 1ET-757 Drawing 2

  • Microprocessor-controlled for high accuracy and flexibility
  • Two separate outputs for outdoor and return air damper actuators with an option to select one actuator
  • Dry bulb or Enthalpy Controller input
  • Indoor air quality sensor analog input
  • Terminal blocks for inputs of G, Y1, Y2, W1 & W2 from thermostat and outputs B, C1, C2, H1 & H2 to the A/C equipment
  • Relief exhaust fan relay output
  • Free cooling hour counter output for saving energy verification
  • On-board potentiometers for easy field setup and adjusting of:
    • Minimum outdoor air damper position
    • Air handling unit supply air temperature
    • Relief exhaust fan activation
    • Indoor air quality high limit
  • On-board LED status indicators for:
    • Free cooling activation
    • Relief fan operation
    • Indoor air quality high limit
    • Control operation, faults and diagnostics
  • Indoor Air Quality requirement override cooling demand
  • Built-in 45-second indoor fan purge delay
  • Use the outdoor air as an emergency cooling stage after 30 minutes if mechanical cooling does not meet the cooling demand
  • Self-configuration for the installed sensors during start up of the controller
  • Mounted in snap-track for easy installation


E-610

The E-610 may be used as a simple temperature controller, providing on/off relay output for fans, heaters, shut off valves and alarm systems. Because of its software adjustable parameters, the product is highly customizable - an ideal solution for many OEM temperature control applications.

buton download pdf

  • Inexpensive, microprocessor based design
  • Relay output, SPDT 1A contact
  • Anti short cycle time delay
  • Set includes 10 k thermistor,and mounting track

Specifications - ET-610

The E-610 is a temperature controller with the ability to act as an ON/OFF temperature thermostat.The device is capable of fully stand alone operation. The unit may be programmed(preset in the factory) in one of three control modes:

(a) temperature range mode in which it will turn ON the output relay between two defined temperatures

(b) set point mode for heating mode iin which it will turn ON below adefined temperature and OFF above a defined temperature

(c) set point mode for coolingmode in which it will turn ON above adefined temperature and OFF below a defined temperature


ET-788

The ET-788 relay board is designed to convert 24VAC control signals to 240VAC dry contacts to operate 3-speed fans, compressors, heater relays, and other line voltage devices.

buton download pdf buton download drawing

  • PCB relay design to reduce wiring and control panel size
  • Suitable for up to 5 control circuits
  • Separate terminals (10 & 11) for electrical heater airflow switch initiation
  • LED for power status indication
  • 24VAC coil voltage
  • 10 AMPS @ 240VAC relay contact rating
  • SPST, normally open contact
  • Dimensions: 2.75” x 3.50” x 0.75”
  • Board supplied with four panel-mounting studs


ET-854

The ET-854 relay board is designed to convert 24 and 240VAC control signals to 240VAC dry contacts to operate 3-speed fans, compressors, heater relays, and other line voltage devices.

buton download pdf buton download drawing buton download drawing

  • PCB relay design to reduce wiring and control panel size
  • Suitable for up to 6 control circuits
  • 24VAC and 240VAC coil voltage
  • 5 AMPS @ 240VAC relay contact rating
  • SPDT, normally open contact
  • Dimensions: 3.25” x 4.65” x 0.75”
  • Board supplied with snap track for easy installation


Series EKB

Series EKB: 3⁄4” Disc Thermostat

The sealed design of EKB provides moisture resistance for high humidity environments.

Automatic reset for high and low temperature applications and manual reset for high limit temperature. The switch opens or closes its electric contacts on temperature rise.

Surface and tube mounting options with a wide variety of terminals, lead wires and mounting options provide excellent design flexibility.

Used in refrigerators, air conditioners, Ice makers freezers, as well as defrost termination and fan delay control.

Temperature range: -30C to 80C (-22F to 176F)
Contact rating: SPST and SPDT with 5A to 25A@ 120/240VAC

bouton download pdf

Series EKB

Series EKB

Series EKB


ekd series

Series EKA: ½” Disc Thermostat

EKA series is a compact design, auto and manual thermostat for controlling or limiting temperature changes.

The switch mechanism is actuated by a snap-action bimetal disc, which opens and closes a set of electrical contacts when predetermined temperature is reached. The bimetal disc is electrically and thermally isolated from the switch.

Different mounting configurations are available for maximum design flexibility: surface mount, air-stream and duct mounts.

Used in boilers, heaters, vacuum cleaners, stoves, dryers, dishwashers and air conditioners.

Temperature range: -30C to 170C (-22F to 338F)
Contact rating: SPST contact with 16A@120/240VAC

bouton download pdf

Series EKA

Series EKA

Series EKA

Series EKA


Series EKC

Series EKC: 3⁄4” Disc Thermostat (High Temperature)

EKC is designed for heavy electric load, with a variety mounting flanges and terminal configurations.

The snap action of the bimetal disc provides high speed contact separation ensuring long contact life cycle and eliminating contact chattering.

EKC-0200 series is a narrow differential, adjustable temperature controls for applications where field adjustment is required such as electric water heaters.

Widely used in HVACR equipment, vending machines, dryer and heaters.

Temperature range: -30 to 170C (-22F to 338F)
Contact rating: SPST and SPDT with up to 35A@120/240VAC

bouton download pdf

Series EKC

Series EKC

Series EKC

Series EKB


Series EKC-200

Electric Water Heater Thermostats and Limits

Surface Mount Temperature Sensing Controls

bouton download pdf

  • High electrical capacity.
  • Snap-Action contact.
  • Long life-proven reliability
  • Adjustable control or manual reset styles
  • UL and cUL

Series EKC-200

EKC-202

EKC-203

EKC-200, Description


EWK

With a high current capability switch of SPST or SPDT. There is a narrow differential and a forced OFF function. This kind of thermostats can be used in direct current (DC) with inductive loads.

WK-B and WK-C series with bottom outlet terminals are available.

Thermostats with a fix operating temperature(without a shaft) for air conditioner defrosting are also availabe.

Available temp, range: -35~+40°C

Adjustable temp, range: Max.20°C

Differential: Min.2°C

bouton download pdf

img1

img2

img3

Room air conditioners, Freezers, Automobile air conditioners.


EWD

Terminal C-L cut-in at temperature rise. Terminal L-H of auxiliary switch cut-out when the shaft turned to OFF point. Terminal C-L can be cut-out at OFF point, and can be forced ON at ON point. The ON temperature is constant at any position from Warm to Cold, the OFF temperature is adjustable. This behavior assure an automatic defrost function.

The WD-R series with an internal bellows heating resistance connected to C-L, is able to be used at cross-ambient in a refrigerator.

Constant cut-in temp, range: +2~+8°C

Available OFF temp, range: -36—4°C

Adjustable temp, range: Max.l9°C

Differential: Min.8°C

bouton download pdf bouton download pdf

Refrigerators.

 


 

EWP

Terminal C-L Cut-in at temperature rise. With SPST or SPOT, and an additional auxiliary switch. There are forced OFF and/or PD points. Type WP-T with two-spring mechanism is a wide differential range.

Available temperature range: -36~+15°C

Adjusting temperature range Max.25°C

Differential: WP(5~14°C) 5-25 °C WP-T (10-25 °C)

bouton download pdf

img1

img2

img3

Refrigerating/freezing devices, Automobile air conditioeing


Terminal 3-4 closes at temperature rise

In general type KP is classified into 2 basic versions:

Version A: KP with standard switching differential

Version B: KP with wide switching differential

Rating at 250 V 50 Hz

3-4: 6(6)A

img1

img2

img3

Operating range: -40 to+40°C

Adjustment range: Vers ion A: 4 to 30K; Version B: 5 to 15K.

Switching differential: Version A: 3 to 14K; Version B: 10to25K.

Capillary type: Shape A (standard); Shape B (on request)

Refrigerating/freezing devices Automotive air conditioning


ekd series

Temperature control with S.P.S.T. switchand auxiliary switch for off position. Automatic defrost function by constant cut-in value

Terminal 3-4 closes at temperature rise

Terminal 3-6 opens in OFF position

Rating At 250 V 50 Hz

3-4: 6(6)A

3-6: 6(6)A

bouton download pdf

img1

Control shown in position COLD according to standard type, other dial shaft positions on request.

img2

img3

Operating range: -32 to +6°C

Adjustment range: 4 to 18K.

Constant cut-in value: +2 to +8K.

Capillary type: Shape A (standard); Shape B (on request)

Refrigerators


ekd series

Temperature control with S.P.S.T. switch and signal switch.

Terminal 3-4 closes at temperature rise

Terminal 3-6 closes when warning temperature has been reached

Rating At 250 V 50 Hz

3-4: 6(6)A

3-6: 0.1A

bouton download pdf

img1

Control shown in position COLD according to standard type, other dial shaft positions on request.

img2

img3

Operating range: -40 to +40°C

Adjustment range: 4 to 30K

Switching differential: 3 to 14K

Signal differential: 4 to 7K

Capillary type: Shape A (standard); Shape B (on request)

Freezers


ekd series

Constant cut-in thermostats for explosive area.

This is a special designed type with SPST switch plus an aux switch. It is an "n" type apparatus in accordance with the standard IEC79-15. It can prevent the possible explosion when the switch body is located in the explosive gas mixed air. Ex approval of China was obtained and VDE Ex test was past.

Maybe with an internal bellows heating resistance connected to C-L terminal to enable to be used at cross ambient in a refrigerator.

bouton download pdf

img1

Control shown in position COLD according to standard type, other dial shaft positions on request.

img2

img3

Constant cut-in temp, range: +2~+8°C

Arailable OFF temp. Range: -36—4°C

Adjustable temp, range: Max. 19°C

Differential: Min. 6°C

Refrigerators.


E-624

Duct type temperature sensor, NTC Thermistor (10k) with 42 probe.

buton download drawing


E-626

The E-626 is a NTC thermistor type sensor. This sensor provides a predictable output over a specified temperature range to meet user’s required input values.

E-626 Thermistor offers high accuracy and interchange ability over a wide temperature range.

buton download pdf

Specifications E-626

Curve Table


E-652A

The E-652A transducer offers inexpensive yet accurate true RMS monitoring of AC current in one circuit.

This product is ideal as a precision AC load transducer for Control and Energy Management applications.

Combined with a standard 5A CT the loop powered E-652A provides a convenient tool for accurate load monitoring in any electrical equipment.

buton download pdf

  • Highly accurate, true RMS measurement.
  • Self powered from the 4 - 20 mA loop.
  • Robust construction (potted box).
  • Compact size and easy wiring.
  • Ideal for Control and Energy Management applications.
  • Power: Standard 4-20 mA loop; voltage 8 - 35 VDC
  • Current Input: Wire current input through CT up to calibrated Range. Unit may be wired off a secondary 5A CT for higher input ranges.
  • Output: 4-20 mA loop (sinking); max. impedance 750 ohm @24VDC (barrier strip terminal provided).
  • Accuracy: TRMS, 0.3% FS for 0-5A & 0-10A ranges, 0.5% for other ranges.
  • Enclosure: Potted plastic box L=3”, W=1.1”, H=0.4” + CT height, panel mount ready. Interfacing CT permanently attached(non universal version); Dielectric test (input/output) - 4 kVRMS

The E-652A is a precision current transducer that performs true RMS current measurements in one AC circuit wired through an interfacing CT mounted on the top of the enclosure.

The E-652A may be ordered for various current ranges. The 0-5A and 0-10A current ranges feature a very high accuracy CT providing 0.3% accuracy (full scale). Other standard ranges include 30A, 50A and 100A. The 5A calibrated i-SnailÔ-A can be applied to the secondary wire of a 5A CT thus extending the metering range as required.

The E-652A is powered from the 4 -20 mA current loop (it acts as a ‘two wire loop device’). It will accept a wide range of loop excitation voltages, typically 24 VDC. The unit is hermetically potted in a small plastic enclosure equipped with two mounting holes. A barrier strip terminal is provided for the output wiring.

The E-652A does not include a built in CT and is equipped with spade connectors allowing remote installation of various Elkor miniature CTs (MCTA and MSCT).

E-652A, Product description


E-652V

The E-652V offers an inexpensive means to monitor any electrical load.

This product is ideal as an AC load transducer for Control and Energy Management applications.

The built-in CT and self powered feature combine to make an easy to install, robust solution.

buton download pdf

  • 0-5V DC Output
  • Self powered
  • Robust construction (potted box)
  • Compact size and easy wiring
  • Power: Self powered by line current
  • Input: Wire current input through CT up to calibrated range:
    0-10A AC
    0-25A AC
    0-50A AC
    CT Wire Window: 14.5mm (0.570”)
    Frequency: 50 or 60 Hz
  • Output: 1% of full scale.
  • Accuracy: TRMS, 0.3% FS for 0-5A & 0-10A ranges, 0.5% for other ranges.
  • Enclosure: Potted plastic box L=3”, W=1.1”, H=0.4” + CT height, panel mount ready. Interfacing CT permanently attached; Dielectric test (input/output) - 4 kVRMS

The E-652V is a simple self power AC current transducer that provides a 0-5V analog signal proportional to the AC current flowing through the CT. Available in three ranges, the i-SnailÔ-V is calibrated to AC sine wave. There is no need for input current configuration nor trimming, saving time and confusion in the field.

The transducer is enclosed in a fire retardant ABS box and encased in potting epoxy to withstand moisture, dust and vibration. The integrated mounting tabs provide an easy means to install the unit on a wall or within a control panel.

The E-652V is ideal for load monitoring without the need for an external power supply. Two signal wires are all that are needed to obtain a linear, 0 to 5 V DC output voltage that may be easily interfaced with PLCs and DDC SCADA systems.

The E-652V includes an on-board CT with a 14.5mm (0.570”) wire window that can accommodate up to AWG #2. The available input ranges are 0-10A, 0-25A and 0-50A. Multiple turns of the primary wire may be used to alter the input range.

Where XX specifies the full scale input current (10, 25, 50 Amps AC)


ETM-619

Electronic digital timer, programable (weekly & daily).

buton download pdf

  • LCD time display
  • LED indication ON
  • Manual ON/AUTO/OFF
  • Temporary override
  • Lithium batteries for memory back up

PROGRAM SETTING:

  • 6 ON/6 OFF
  • Supply voltage: 120VAC, 220VAC, 24VAC/DC, and 12VDC
  • Frequency: 45-60Hz
  • Own consumption: Approx. 7A
  • Contact rating for: 16A/250V resistive, 8A/250V inductive
 TM-619 & TM-619L 20A/120V resistive,
 8A FLA/250V, 16A/30VDC
 0.5HP 250V OR 125V
  • Contact rating for: 30A/250V resistive
 TM-619H 2HP, 12FLA, 250V
20A, 240V BALLAT
 15A, 125V TUNGSTEN 
5A, 250B TUNGESTEN
  • Switching command: 1 minute
  • Admissible ambient temperature: -10 degree C to 55 degree C


ecm-102
  • Delay on Make & Delay on Break timers
  • Ideal for motors, compressors and other devices start up and staging
  • Reduce power surges in multiple compressor applications
  • Compact 2” X 2” and easy mounting
  • Help protect compressor from damage due to rapid short cycling
  • Work with anticipator-type thermostats
  • Adjustable delay 0.03 to 10 minutes
  • Contact: SPST (NO)
  • Operating voltage: 19 - 250 VAC/VDC
  • Rated current: 1.0A
  • Inrush current: 10A
  • Minimum current: 40mA
  • UL & cUL

buton download pdf


ecm-203
  • Delay on Make & Delay on Break timers
  • Ideal for motors, compressors and other devices start up and staging
  • Reduce power surges in multiple compressor applications
  • Compact 2” X 2” and easy mounting
  • Help protect compressor from damage due to rapid short cycling
  • Work with anticipator-type thermostats
  • Adjustable delay 0.03 to 10 minutes
  • Contact: SPST (NO)
  • Operating voltage: 19 - 250 VAC/VDC
  • Rated current: 1.0A
  • Inrush current: 10A
  • Minimum current: 40mA
  • UL & cUL

buton download pdf


eks

Applications

Furnace, Heaters, Heat Pump, and Air Conditioners

bouton download pdf

  • Control the operation of heating elements and blower fans in electric furnaces and heat pumps.
  • Combine a solid state positive temperature coefficient (PTC) heater.
  • 24V solid state heater input.
  • Wide variety of switch configurations are available include SPST, SPDT and DPST.
  • Multi relay mounting and up to 5 timings.
  • Max working temperature :185C
  • Electrical rating (resistive): 25Amps @ 120/250 VAC, 50/60 Hz.
  • Agency: UL and cUL.

Specifications

img1

img2


Digital Thermometer and Hygrometer

buton download pdf

  • Measure and display the indoor/outdoor temperature and indoor humidity
  • Automatically memorize the Max./Min. values of the indoor/ outdoor temperature and indoor humidity
  • Switch between °C / °F
  • Clock function and alarming function
  • 12/24 hour mode switch
  • 8 minutes snooze function
  • Recovery function on the Max./Min. values
  • Indoor temperature measuring range: -30°C~+50°C (-22°F~122°F)
  • Outdoor temperature measuring range: -50°C~+70°C(-58°F~158°F)
  • Indoor humidity measuring range: 20%~99% (Relative humidity)
  • Resolution: Temperature: 0.1°C; Humidity: 1% RH
  • Power supply: one AAA alkaline battery
  • Operation environment: Temperature: 0°C~50°C; Humidity: 5%~85% RH
  • Automatically memorize the Max/Min values of indoor/outdoor temperature and indoor humidity
  • Press IN/OUT key to switch between indoor/outdoor temperatures
  • Press MAX/UP key to display memorized indoor/outdoor max temperature and indoor max humidity
  • Press MIN/DOWN key to display memorized indoor/outdoor min temperature and indoor min humidity
  • Press RESET to clear memorized value and start to memorize new max/min value
  • Press 12/24 to switch the time displaying modes
  • When alarm sounds, pressing SNZ key will activate the snooze function, and display "img "
  • Switch °C / °F to display Celsius or Fahrenheit
  • Clock set: Press Mode key for 3 seconds into time setting mode. When "hour" blinks, press MAX/UP key and MIN/DOWN key to increase or decrease the "hour" value. Pressing the key continuously makes the "hour" value change faster. Press Mode key again to confirm, and then "min" blinks, press MAX/UP key and MIN/DOWN key to increase or decrease the "min" value, press Mode key to exit the set of clock
  • Alarming set: Press Mode to display the sign of "img ", then press Mode key for 3 seconds into alarming set, the way of setting the value is same as clock set.


Portable Data Recorder

Simply Set Up And Record In Real Time With Remote Sensor Or Without & Use The Internal Sensor. Download To Your Computer Via The USB Cable Connection Analyze And Save Data.

buton download pdf

  • Rechargeable Lithium Battery
  • USB Powered Option
  • Adjustable Cycles
  • Upper and Lower Adjustable Alarm Limits
  • USB Data Exchange & Power Source
  • Windows98, NT, 2000, XP Compatible
  • Data Analysis With Curves & Graphs
  • Display Alarm Limits
  • Word Format File Save and Printing
  • Adjustable Recoding Cycle From 2 Seconds Over 24 Hr
  • May Be Automatically Distributed For Recording Duration
  • 16000 Point Recording
  • -40C to +70C External Sensor Range
  • -30C to +50C Internal Sensor Range
  • Up To +- .5C Resolution
  • NTC Sensor
  • IP65 Enclosure
  • Device Environment –30C to 50C 15% to 85% R/H


EKC-1

Temperature Data Logger (Reusable Cartridge)

buton download pdf

  • ERC‐1+ is a data logger with internal sensor that can be used multiple times
  • Reliable, compact in size and easy to install
  • Easy data transmission by inserting the recorder in the card reader interface. Data can be downloaded to any computer with USB interface.
  • ERC‐1+ designed for many applications where close temperature monitoring is needed such as laboratory, foodstuff, medical facilities and refrigerated transportation
  • ERC‐1+ is used for applications complying with HACCP (Hazard Analysis and Critical Control Point) System Certificate.
  • Power supply: One CR2450 lithium battery
  • Temperature measuring range: ‐40.00C~+70.00C
  • Accuracy: ±10C
  • Displaying resolution: 0.1
  • Recording cycle: 10 seconds~16mins continuous setting
  • Record time length: 89 days (MAX)
  • Recording capacity: Temperature: 8000 points (Max.)
  • Ambient environment of shell: Temperature: ‐350C~+700C; Humidity: 0%~95%
  • Data output: Connect the computer with USB interface to transfer data
  • Protection: IP65


ETM-2024

Temperature Indicator C/F)

buton download pdf

  • Power Supply : 24 VAC
  • Displaying mode: Three digit LED + indicator light
  • Temp. measuring range: -49°C~99°C (-49F~199F)
  • LED displays "HHH" when exceeding upper limit temp. or probe short circuit
  • LED displays "LLL" when exceeding lower limit temp. or probe open circuit
  • Switch between C and F by DIP switch (DIP3)
  • One channel temp. measurement
  • Resolution: 0.1
  • NTC wire length: 2 M (6.5 ft)
  • Product size: 70 x 33.5 x 68mm
  • Mounting-hole size: 58 x 26mm


ESD-1

 

SOLAR DIGITAL THERMOMETERS (C/F)

buton download pdf

  • Function: ON/OFF switch, °C/°F switch
  • Backup Power: AAA battery x 1
  • Material: ABS case, stainless steel bulb
  • Wire Length: 1.2 meters (48")
  • Case Color: Black
  • Temperature Range: -50 to 70°C&°F
  • Resolution: 0.1°C
  • Package: 1pc/white box
  • IP Rating: IP45
  • Product Size: 114mm x 28mm
  • IMounting-hole: 105.5mm

 


 

EASM1

Analog scaling module

buton download pdf

  • 24V AC operation
  • Output can sink input’s pull-up voltage
  • Optional Zero & Span potentiometers
  • Small size 1.10" by 2.19"
  • Two mounting options
  • Analog 0 to 5V DC & 0 to 10V DC scaling
  • Rescale non - standard sensors
  • Rescale non - standard voltages

The EASM1was designed as an analog signal scaling module to rescale control voltages or sensor signals to meet the input requirements of the various controllers. The EASM1 will also allow you to use existing sensors and scale the EASM1's output to match your controller’s input requirement. The EASM1's output can sink the controller’s input pull-up voltage on the application inputs. The EASM1 can be factory calibrated to your specific signal requirements. It can be snap - track mounted for panel use or be potted with detachable terminal block for field use.

The EASM1 uses a half wave rectifier for 24V AC power input, with terminal 2 being common for the power supply, input common and output common. The input can be factory configured for voltage, current, or sensor signals either requiring a pull-up voltage or a load resistance. The signal then passes through two op-amp stages where it is scaled to the desired output signal.

img

img


LF10

The LF10 pressure switches are used to regulate the tank pressure between two preset values on electrically driven air compressors. They are available with an unloader valve, which prevents compressors from starting under load, and an auto-off disconnect lever for manual cut off the compressor. A four port manifold style is available which provides a means for easy mounting of valves and gauges.

buton download pdf

Specifications E-626

Curve Table


LF10

The rugged LF17 pressure switch is designed for the demanding requirements of larger, heavy duty commercial air compressors (up to 250psi). The sturdy painted steel case and cover resist the harsh conditions encounted in industrial applications. This style is available with an unloader valve to prevent the compressor from starting under load.

buton download pdf

Specifications E-626

Curve Table


LF16

LF16 Water pressure switch provide time tested, reliable control for automatic water supply systems. The switch is universally acceptable for use as original equipment on water pumps or pumping systems.

buton download pdf

Specifications LF16

LF16


LF16

The LF17-W is a ruggedized water pressure switch designed to meet the requirements of heavy duty industrial pumping applications.

buton download pdf

Specifications LF17-W

LF17-W

LF17-W


lf37

LF37 diaphragm pressure switch is available for various sumps, effluent, and sewage application to control the liquid level. Various switch settings are available for to turn-on or turn-off the pump. The diaphragm pressure sensing design make it more reliable than traditional float ball mechanism.

buton download pdf

Specifications LF17-W

LF17-W

LF17-W


LF10-W

LF10-W pressure switch provide time tested, reliable control for automatic water systems. The switch is universally acceptable for use as original equipment on water pumps or pumping systems. Lf10-WR can prevent thepump from starting whenever the system falls considerable below cut-in pressure. Upon the restorations of the water supply, it will automatically cut-in. A manual reset level is depressed until a build up of system pressure permits automatic operation. Its simple design makes it easy to use for professionals and nonprofessionals alike.

buton download pdf

Specifications LF17-W

LF17-W

LF17-W


LF31

LF31 pressure switch was designed for use in the HVAC industry where safety and reliability ar essential. Despite the design intent this series has proven to be a viable solution for many pneumatic applications as well. Available in vacuum, differential and pressure models with fine silver or gold cross bar contacts, the LF31 is capable of detecting pressures as low as .05 inches of water. Factory calibrated units maintain set point tolerances of +/-10% over a temperature range of -40 F to 185 F due to its molded silicone diaphragm and the stability of its glass filled polyester body. LEFOO offers multiple electrical terminations and mounting options as well as bleed holes and 3 different size orifices. This switch series is not only the leading product in the market offering the highest quality and reliability but is also the most economical.

buton download pdf

Specifications LF31

LF31

LF31


LF32

LF32 switch is capable to sense tiny pressure change and widely used to control the flue of aerator, to monitor and fan and air conditioner; it is also for over heating protection and frost protection in industrial cooling system. Due to its outstanding design, the setpoint can been adjust visually.

buton download pdf

Specifications LF32

LF32

LF32


LF31

LF31 pressure switch was designed for use in the HVAC industry where safety and reliability ar essential. Despite the design intent this series has proven to be a viable solution for many pneumatic applications as well. Available in vacuum, differential and pressure models with fine silver or gold cross bar contacts, the LF31 is capable of detecting pressures as low as .05 inches of water. Factory calibrated units maintain set point tolerances of +/-10% over a temperature range of -40 F to 185 F due to its molded silicone diaphragm and the stability of its glass filled polyester body. LEFOO offers multiple electrical terminations and mounting options as well as bleed holes and 3 different size orifices. This switch series is not only the leading product in the market offering the highest quality and reliability but is also the most economical.

buton download pdf

Specifications LF31

LF31

LF31


LF32

LF32 switch is capable to sense tiny pressure change and widely used to control the flue of aerator, to monitor and fan and air conditioner; it is also for over heating protection and frost protection in industrial cooling system. Due to its outstanding design, the setpoint can been adjust visually.

buton download pdf

Specifications LF32

LF32

LF32


lf37

LF37 diaphragm pressure switch is available for various sumps, effluent, and sewage application to control the liquid level. Various switch settings are available for to turn-on or turn-off the pump. The diaphragm pressure sensing design make it more reliable than traditional float ball mechanism.

buton download pdf

Specifications LF17-W

LF17-W

LF17-W


LF40-01 Air Actuated Switch

LF40-01 can be used togethr with an air button (also called as Actuator ) for remote control purpose. It is widely used in food waste disposers, pumps for swimming pools and spas, hot tubs, sanitary equipments, out door machines,medical equipments ect. As remote control switch, it i small enough to fix in the control box of the engine. Used as a remote control the air switch has two actions:

  1. Momentary action: when the air button is pushed, the air switch is actuated. When the air button is released, the air switch will also be released. This is the way the basic pressure switches are working.
  2. Alternate action (also referred to as latching or bistable): the first pushing on air button actuates the air switch, and the air switch keep acuating when air button is released. A second push on the air button will release the air switch.

buton download pdf

Specifications LF40-01

LF40-01

LF40-01


LFS-01 Pressure Switch

LFS-01 pressure switch is applied to detection of negative pressure, widely used in electrical appliance such as the vacuum cleaner, paking etc. It provides solder pin connections and is especially designed for mounting on "Printed Circuit boards".

buton download pdf

Specifications LFS-01

LFS-01 Pressure Switch

LFS-01 Pressure Switch


LFS-02 Pressure Switch

LFS-02 pressure switch is designed as an economical interface between pressure systems and Printed Circuit Boards. This switch can be used as a gauge or differential pressure switch with almost no hysteresis. Features of this switch include a body design that allows the pressure ports to be rotated, various terminal styles including wire leads. Strong and reliable, LFS-02 is a popular choice for many manufacturers.

buton download pdf

Specifications LFS-01

LFS-01 Pressure Switch

LFS-01 Pressure Switch


LF25  Pressure Switch

LF25 pressure switch is to control the pressure of application with higher current catacity. It is widely used in stream cleaner, stream iron and othe pressure control system. It provides SPST or SPDT contact form and switch deadband (also referred to as mechanical differential or hysteresis).

LF25 switch utilize high-quality miniature snap-action switches. The switch is diaphragm operated. Diaphragm material can be selected for the opering medium, temperature range and other parmeters. During the development of a specification, acuation point can be adjusted by the designer, in production, factory setting is required.

buton download pdf

Specifications LF25

LF25  Pressure Switch

LF25  Pressure Switch


LF20  Pressure Switch

The LF20 pressure switch is specifically designed to stand up to extended duty applications. This switch is factory set but capable of field adjustment. It features different diaphragms for compatibility with a wide variety of fluids, and various terminations including a Metri-Pack connector that forms a tight seal when connected. Among the outstanding design benefits are its durable construction, compact size, and enhanced set point integrity.

It can be widely used for pool and spa, anti-skid braking systems, water pump systems, and dental air compressors, heavy construction, off road applications and other pressure control systems.

buton download pdf

Specifications LF20

LF20  Pressure Switch - orderRef1

LF20  Pressure Switch - orderRef2